- GB10 Gebruiksaanwijzing
Sensor unit
The AFJ3 gives vital information and allows you to remotely monitor power eliminating the need for manual power audits as well as providing immediate alerts to potential problems. It has been integrated into the AFI2 web interface with its own "Power Management" menu. More Sensor unit can be connected to a single base unit depending on what readings are required.
Data collected over time using the AFJ3 can also be viewed using the built in graphing tool. IP-enabled power monitoring capable of monitoring/measuring:
- Phase Line Voltages
- Current
- Power Factor
- Active Energy
- Active Power
Create alert notifications using the Rich Notification Suite and choose any combination of these alert options:
- SMS
- Email
- MMS
- Telephone call
- Fax
- SNMP
- Relay switch automates corrective action.
This four-wire sensor is encased in sturdy white plastic and mounts on a 35mm DIN rail. Order it for 110 or 220 power supplies. It functions with single- or three-phase circuits, and meets international standards for active and reactive energy - IEC 62053-21 and IEC 62053-23, respectively.
It is currently possible to monitor 14 readings from AFI2 from the AFJ3 web interface. List of 3 Phase values:
3 Voltages (each phase line ±0.5%)
3 Amps (each phase line ±0.5%)
3 Power Factor (each phase line ±0.2%)
3 Active Power (each phase line ±0.5%)
1 Frequency ±0.2%
1 Active Energy ±1%
Monitor
With the AFI2, monitor the physical environment and receive alerts of any disturbances, such as unauthorized intruders, security breaches, high temperatures, smoke, water leakages, power outages and more. Compatible with all of the Pro range of Intelligent Sensors it provides a complete environmental, access control and security monitoring solution for up to 500 connected sensors. The AFI2 has a Linux Operating System running an iMX25 CPU. An additional 2 Gigabytes SD card can be installed to provide greater storage capacity.
Networked Monitoring
It is TCP/IP compliant and runs lighttpd web server including https (SSL), Bash, Perl, Telnet, PHP, Email and Nagios. The AFI2 has an easy-to-use web-based user interface for sensor configuration, data collection and extensive graphing. Complete SNMP functions such including SNMP v3 encryption are supported. The AFI2 also supports Modbus Master/Slave, Modbus RTU and Modbus over TCP/IP creating a unique, easy to configure Modbus to SNMP gateway. The web-based interface is written in PHP allowing end-user changes such as language translation. The AFI2 has a battery backed time of day clock for accurate record keeping.
| Sensor unit | |
| Fase: | 1 |
| Rated Voltage (Un): | 230 VAC |
| Voltage range: | 0.7~1.3Un |
| Basic current (lb): | 10A |
| Maximum current: | 100A |
| Operational Current Range: | 0.4% Ib- lmax |
| Over Current Withstand: | 30Imax for 0.01s |
| Internal Power Consumption: | ≤2W / 10VA |
| Frequency(Hz): | 50~60Hz ±10% |
| Accuracy Class: | Voltage: ±0.5% |
| Amps: ±0.5% | |
| Frequency (Hz): ±0.2% | |
| Max Diameter Cable: | 11.5 mm |
| Communication Type: | RS485 |
| Communication Standard: | Modbus |
| Operating Humidity: | ≤ 75% |
| Operating Temperature: | -10°C - +50°C |
| Dimensions: | 100mm(L) x 76mm(W) x 65.5mm(H) |
| Weight: | 350 gram |
| Standards: | IEC 62053-21 |
| Monitor | |
| Expansion Boards: | 8 Port Intelligent Sensors Module |
| (E-Sensor8) 16 Port Dry Contacts Module | |
| (E-opto16) (Maximum of 500 Sensors) | |
| Two Door, Door Control Unit (DCU) Extendable up to 1,000 Feet or 300 meters | |
| Expansion modules are daisy chainable | |
| Components: | Manufactured using highly integrated, low power surface mount technology to ensure long term reliability |
| CPU: i.MX25 Processor | |
| On-board SD Flash Slot | |
| Output: | Ext. Speaker Out, 2.5” jack (Analog) |
| Mic Out, 2.5" jack (Analog) (For modem application) | |
| Mounting: | Rack mount brackets included |
| Compatible with DIN and rack mount trays | |
| Expansion Ports: | 4x RJ-45 Expansion Ports |
| 115.2K BPS Data Transfer Rate | |
| Simultaneous functionality between Expansion Ports & RS485 port threshold status | |
| Inputs: | 8x RJ-45 Sensor Ports |
| 4x RJ-45 Expansion Ports | |
| 1x USB 2.0 Modem Port | |
| Audio In (Analog) 2.5" jack | |
|
RS485, 2 Pin Terminal box, (used for Modbus) * USB Digital Cameras are NOT compatible with the AFI2 |
|
| Status Indication: | LED indication for Power |
| LED for Network Connectivity | |
| LED for sensor online and threshold status | |
| MTBF: 400,000 Hours | |
| Power Consumption: | Typical 5.025 Watt, 0.67A |
| Power Requirements: | Voltage 7.0 – 9 VDC, 3Amp |
| Dimension: | Size 8.5" x 5.43" x 1.80" |
| 1U Rack Mount Standard | |
| Weight: | 1 Kg |
| Goedkeuring: | CE, RoHS en WEEE |